Type A earth leakage relay - 2 DIN modules
The new range of type A earth leakage relays with separate toroid provides maximum safety and reliable protection in compliance with EN 60947-2 Annex M. Tripping current IΔn adjustable from 30mA to 30A. Settings by means of dip-switch and trimmer protected by sealable front panel. Dual TRIP relay. Connection by means of external closed-core or split-core toroids of the TDC-TDA series.